Is Your Gas Meter Big Enough for a Whole-Home Generator?

Do I need a bigger gas meter for a generator
  • June 1, 2025

How to tell if your gas meter is big enough for your new generator.

A generator requires both adequate gas pressure and sufficient gas flow, and having one does not guarantee the other.  Inadequate gas flow or pressure is one of the leading causes of generator startup failures, often caused by improper sizing during the installation and home evaluation. We see it frequently on service calls. A generator may run perfectly during its weekly exercise, only to fail when placed under a full electrical load.

At Guardian Home Generators, we do the homework upfront, calculating your home's gas requirements to ensure your generator has the fuel supply it needs to perform reliably when it matters most.  Curious about your current meter, or concerned it might be undersized? Here's how to check it yourself.

Find your meter's capacity and pressure
To find flow capacity, look for a number followed by CFH (cubic feet per hour) or a model number such as AC-250 or AL-425 on the front of your meter.

Some gas meters have a white background behind the dials, indicating low-pressure service (ounces), while others have a red background, indicating high-pressure service (pounds).  More on this below.

Is your meter big enough?
Generac and Kohler air-cooled generators can require approximately 300 CFH (300,000 BTU/hr) of natural gas, depending on the model. The meter pictured on the left is rated at just 250 CFH, meaning this homeowner will need additional meter capacity to support the generator and other gas appliances.

Use our Gas Meter BTU Calculator for Whole-Home Generators to estimate your home's total gas requirements, including your generator.

Keep in mind: Your calculations should be reasonably accurate, but they don't need to be exact. The calculator assumes every gas appliance is operating at full capacity simultaneously, which is unlikely to occur in normal household use.

What if you need a larger capacity meter?
Here in North Texas, most customers have Atmos as the gas provider.  Atmos provides meter upgrades at no charge, and upgrades can be completed before or after generator installation.  Simply call the phone number on your bill and let them know you need a meter upgrade.  Atmos typically will not tell you what size meter you need; that's why we are here to assist you.

Low pressure vs. high pressure, and do I need to convert my system?
Most generator installations do not require converting to high-pressure gas. 
Although we can calculate your home's total gas demand, we cannot reliably determine in advance whether you will need to convert from low-pressure to high-pressure gas service. While the gas utility typically upgrades the meter at no charge, converting to high-pressure service can add $650 to $1,000 for additional gas regulators at the home and generator. Because most homes can accommodate a generator using their existing low-pressure service, we recommend keeping your current system unless testing under actual operating conditions demonstrates that it cannot supply sufficient fuel to the generator.



Blog Post

Related Articles

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Suspendisse varius enim in eros elementum tristique.

How much does a whole home generator cost in North Texas?

October 10, 2026
What Goes Into the Cost of a Generator Installation? A whole-home generator installation from Guardian Home Generators...

Calculating the size of your backup generator

June 30, 2026
How Much Power Does Your Home Actually Use? Calculate the size of your backup generator.